Overview
Pakistan’s power grid, water treatment plants, and gas pipelines rely on Industrial Control Systems (ICS) and SCADA networks that were often designed for reliability rather than security. Over the past two years, the National Counter Terrorism Authority (NACTA) and the National Transmission & Dispatch Company (NTDC) have flagged attempts by state‑aligned APT groups to probe these OT environments. This lesson shows how a Pakistani SOC can build a focused CTI pipeline for ICS assets, using open‑source feeds, Sigma rules, and community tools.
Pakistan’s ICS Threat Landscape
- State‑linked groups have been observed scanning IEC‑61850 and DNP3 ports on provincial substations.
- Ransomware families have begun to include ICS‑aware payloads that tamper with RTU firmware.
- Insider misuse of SCADA workstations remains a risk, especially when default credentials are not rotated.
Building an ICS‑Focused CTI Workflow
- Asset inventory – Use Nmap with the
modbus-discoverands7-comm-discoverscripts to enumerate PLCs and RTUs on the OT subnets. Export results to a CSV. - OSINT harvesting – Monitor the ICS‑CERT advisories, the Exploit‑DB “ics-exploits” tag, and Pakistani‑language Telegram channels that leak SCADA screenshots.
- MISP feeding – Create an ICS‑Intel MISP event type. Tag each indicator with TLP:AMBER+GPU and share it with the community portal at pisa.maahir.io.
- Detection with Sigma – Write a Sigma rule to alert on unexpected Modbus function‑code 6 (write single register) from a non‑engineering workstation.
- Wireshark capture – Capture traffic on the SCADA mirror port and apply a display filter
modbus.func_code == 6 && ip.src != 10.0.0.0/8to spot rogue writes. - Incident reporting – If a suspicious write is confirmed, call the NCCIA cybercrime helpline 1799 and file an NACTA report.
Do / Don’t
- Do rotate default SCADA credentials and enforce network segmentation between IT and OT.
- Do run passive traffic analysis on the OT segment; avoid active scanning that could disrupt PLCs.
- Don’t store SCADA credentials in plain text on workstations that also browse the internet.
- Don’t ignore alerts from Sigma rules—treat each as a potential ICS intrusion.
Takeaway
This week, run an Nmap OT scan on a sub‑net that you are authorized to test, import the discovered devices into MISP, and share the resulting event on pisa.maahir.io. The simple act of making your SCADA inventory visible to the wider Pakistani CTI community dramatically improves early warning for power‑grid attacks.