PISA Pakistan — Community CERT

← ⚙️ Red Team Fundamentals (Ethical)

50. Smart Grid and AMI Pentesting: Red Team Tactics for the Power Sector

⏱ 9 min

Smart Grid and AMI Pentesting: Red Team Tactics for the Power Sector

AMI Architecture and Key Protocols

AMI replaces electromechanical meters with smart meters communicating via DLMS/COSEM, IEC 61850, and IEEE 2030.5. NEPRA is driving AMI adoption across Pakistani cities, expanding the attack surface for red teams.

Attack Surface in Pakistan's Smart Grid

  • Firmware extraction via insecure UART/JTAG, exposing keys.
  • DLMS/COSEM replay to manipulate billing.
  • IEC 61850 GOOSE/SMV injection causing protection‑relay misoperations.
  • USSD‑based remote disconnect abusing back‑office APIs (linked to OLX/Daraz scams).
  • Man‑in‑the‑middle between meters and MDM, intercepting telemetry.
  • Consumer data may be linked to NADRA CNIC, requiring careful handling.

Lab: Firmware Extraction and Traffic Analysis

  1. Identify UART pins with a multimeter/logic analyzer.
  2. Connect FTDI and dump firmware using flashrom/openocd.
  3. Analyze firmware with binwalk to find keys/default passwords.
  4. Capture DLMS traffic in Wireshark (dlms filter) to see getRequest/setRequest.
  5. Replay a billing‑reset command in a sandbox to confirm exploitability.

Exploiting DLMS/COSEM and IEC 61850

  • Use python‑dlms to craft setRequest frames bypassing checksum validation.
  • Scapy‑IEC61850 can inject malicious GOOSE messages to test relay behavior.
  • Map findings to MITRE ATT&CK T0841 (Network Traffic Execution).

Detecting and Mitigating AMI Attacks

  • Enforce mutual authentication for DLMS/COSEM with X.509 certificates.
  • Segment AMI head‑end from corporate networks.
  • Align with PTA and NCCIA 1799 for incident reporting; remediation checklists are at pisa.maahir.io/red‑team/ami‑security.

Do / Don't

  • Do obtain written scope from the utility’s NOC before testing.
  • Don't attempt real customer disconnects or manipulate live protection gear.
← PrevNext →